- 38,900 Btu/hr Cooling Capacity
- 28,500 Btu/hr Heating Capacity
- Desuperheater for Hot Water Heating
- 1000 CFM Airflow Rate
- 2.68 kW at Full Load
- 6000 Btu/hr, 24 GPH Water Heating Capacity
- 4 Feet Head Loss
Vertical Ground Loop
- 1200 Feet HDPE 1.25" Piping
- 6 - 100 Foot Deep Bore Holes
- 7 GPM Flow Rate
- 73 Degree Fahrenheit Ground Temperature
- At Full Load, Loop Temperature
- 108 deg F Incoming Temp
- 97 deg F Outgoing Temp
- 45,000 Btu/hr Heat Dissipated in Loop
- 10 Feet Head Loss
Wilo-Stratos ECO 16 F Pump
- 120 Watts
- At 7 GPM, 24 Ft of Head Loss
Energy Use
- Heat Pump -- 2.68 kW
- Pump -------- 0.12 kW
- Total --------- 2.80 kW
Economics
- Heat Pump Price -------- $10000
- Ground Loop Price
- at $15 per foot ---- $9175
- Pump ---------------------- $500
- Total Cost ----------------- $19675
- Cost With 30% Rebate -- $13773
- Annual Costs with Geothermal ------------- $350
- Annual Costs with AC and Water Heater- $ 1502
- Payback Time --- 9.4 Years